Powermonitor 3000 Master Module 57
Publication 1404-IN007F-EN-P - November 2009
Current sense inputs: I1, I2, I3, I4 Overload withstand: 15 A continuous, 200 A for 1 s
Burden: 0.05VA
Impedance: 0.002 Ω
Max crest factor at 5 A: 3
Starting current: 5 mA
Status inputs Contact closure (internal 24V DC)
Control relay
KYZ output
(1) ANSI C37.90-1989 trip duty
(1) Solid state KYZ - 80 mA at 240…300V DC
Control Relay
(1)
(1)
Meets ANSI/IEEE C37.90-1989 standards for trip duty.
Rating 50/60 Hz AC rms DC
Resistive load switching, max 10 A at 250V
(2500VA)
10 A at 30V and 0.25 A at 250V
Load switching, min 10 mA at 24V 10 mA at 24V
UL 508, CSA 22.2, IEC rating class B300 Q300
Make values, max (inductive load) 30 A at 120V
15 A at 240V
(3600VA)
0.55 A at 125V
0.27 A at 250V
(69VA)
Break values, max (inductive load) 3 A at 120V
1.5 A at 240V
(360VA)
0.55 A at 125V
0.27 A at 250V
(69VA)
Motor load switching, max 1/3 HP at 125V
1/2 HP at 250V
Input and Output Ratings
(1)
(1)
Meets ANSI/IEEE C37.90-1989 standards for trip duty.
Attribute Number of Operations
Mechanical
5 x 10
6
Electrical
1 x 10
5
Input and Output Ratings
Attribute Value