Commands Reference
CoolMaster PRM
13
www.coolautomation.com
© 2011 Cool Automation LTD
Rev 3.8
EXTENSIONS
CoolMaster 4000F PAC-YG Support
In CoolMaster 4000F v2.5.6 or higher to control PAC-YG66 digital I/O device following off command
format is used
off <UID> [N]
N is digital output number 1..6
>off 012 2
OK
>off 012 6
OK
4.1.12 on
SYNOPSIS
on <UID>
DESCRIPTION
Turn on indoor unit UID.
EXAMPLE
>on 102
OK
EXIT CODE
OK
Request Successfully Executed
ERROR:1
Unit with specified UID not found
EXTENSIONS
CoolMaster 4000F PAC-YG Support
In CoolMaster 4000F v2.5.6 or higher to control PAC-YG66 digital I/O device following on command
format is used
on <UID> [N]
N is digital output number 1..6
>on 012 2
OK
>on 012 6
OK